          Introduction to installation specification of current transformer
          1 the installation of the current transformer must be firm. The exposed metal part of the transformer shell should be reliably connected.

          2 The same set of current transformers should be installed in the same direction to ensure that the primary and secondary circuit currents of the current transformers are in the same direction and the nameplate can be easily observed.

          3. The secondary side of the current transformer is not allowed to open circuit. When only one secondary circuit is used for the secondary double-turn transformer, the other secondary circuit should be reliably short-connected.

          4 the low voltage current transformer can not be grounded on the two side. Because the conductors, watt-hour meters and transformers used in low-voltage metering devices have the same insulation level, the highest voltage they can withstand is basically the same; in addition, after the secondary windings are grounded, the insulation level of the primary circuit of the whole set of devices to the ground is reduced, which makes the watt-hour meters or transformers with insulation weaknesses easy to be damaged under high voltage (such as induced lightning strikes). Bad. It is better to reduce the damage caused by lightning damage to two sides.
          Previous:Technical problems easy to appear in transformer test/ Next:How to use the current transformer correctly?
          Products
          Measuring current transformer
          Metering current transformer
          Protective current transformer
          Leakage (residual) protection device
          The zero sequence current transformer
          Voltage transformer
          Transmitter
          Meter
          common problem
          How to use the current transformer correctly?
          Introduction to installation specification of current transformer
          Technical problems easy to appear in transformer test
          Case
          Contact Us

          Address: No. 555 Shenze Road, Dongxi Industrial Zone, Jinhua, Zhejiang.
          Zip code: 321017

          Tel: 0579-82235395 82235362
          Fax: 0579-82235388
          Website: www.sgbuy4u.com

          E-mail: aokai@okdq.cn

          综合亚洲一区二区三区|国产真实夫妇4P交换在线观看|久久精品无码AV天堂|欧美日韩视频一区二区三区|国产精品热久久无码av|欧美亚洲另类国产很色婷婷|在线免费播放一区日本专区